Fire department connection sign requirements serve illustrate things: System type, including a standpipe manual wet dry System demand pressure greater 150psi FDCs service a portion a building multiple buildings
According the Fire Code, access roads be and maintained allow fire apparatus be to within 50 ft (15 m) at one exterior door to within least 150 ft (46m) all exterior portions the story—this increased 450 ft (137 m) the building sprinklered.
Below a summary requirements the 2002-2019 editions NFPA 13 13R, the 2000-2019 edition NFPA 14. more fire protection resources, including free code-based summaries this, visit subscribe www.meyerfire.com/blog.
Q. are IBC/IFC requirements FDC Signs existing buildings? Q. should Fire Department Connection unobstructed all times? Q. to ensure firefighters find use FDC? Q. IFC any specific requirements the FDC area? Q. FDC Signs to reflective? Q. NFPA require FDCs all buildings?
These minimum signage requirements intended provide basic information needed a fire department provide necessary pressure flow a standpipe system. is intended be location indicator, that a biproduct the sign, Section 6.4.5.1 additionally requiring fire department connection be .
On existing buildings, the fire department connection not visible approaching fire apparatus, fire department connection be by approved sign mounted the street front on side the building.
Where fire department connection services multiple buildings, structures, locations, sign be indicating buildings, structures, locations served. Section 6.6 requires required signs be secured a device the building wall corrosion-resistant chains fasteners.
NFPA 13 - Section 8.17.2.4.7.1 fire department connection sprinkler systems be designated a sign raised engraved letters least 1 in. (25 mm) height plate fitting reading service design — example, AUTOSPKR., OPEN SPKR., STANDPIPE.
Proper signage required improve visibility provide information the FDC. NFPA 13 that FDCs have plates ( 16.12.5.8) fitted the pipe raised engraved letters least 1 in height.
A metal sign raised letters less 1 (25 mm) sie be mounted all fire department connections serving automatic sprinklers, standpipes fire pump connections. signs read: AUTOMATIC SPRINKLERS STANDPIPES TEST CONNECTION a combination thereof applicable.
(1) Fire department connections visible accessible. (2) Couplings swivels not damaged rotate smoothly. (3) Plugs caps in place undamaged. FDCs be visible accessible (inspection item #1) — snow bushes are NFPA 25 violation. Images source: Fire Protection Deficiencies (4) Gaskets in place.